• OVT-X3 Overvoltage Release
OVT-X3 Overvoltage Release

OVT-X3 Overvoltage Release

Product description:1. Major function To be assembled with the circuit breaker to achieve overvoltage protection. 2. Parameters and performance Rated operation voltage Ue: AC 240V 50Hz (or 60Hz). Rated insulation voltage Ui: 500V. Overvoltage setting value Uvo

1. Major function

To be assembled with the circuit breaker to achieve overvoltage protection.
 

2. Parameters and performance

Rated operation voltage Ue: AC 240V 50Hz (or 60Hz).

Rated insulation voltage Ui: 500V.

Overvoltage setting value Uvo: 280V.

Release action characteristics: when the main circuit voltage is in the range of (85% ~ 110%) Ue, the release shall be able to keep the circuit breaker to work reliably for long term. When the main circuit voltage is increased to 280 (1 ± 5%) V, the release assembled with NXB-125series circuit breaker should act and trip open NXB-125 circuit breaker. Mechanical and electrical life: the mechanical and electrical life of release is ≥ 4000 operation cycles.


Catalog

OVT-X3 Overvoltage Release Catalog.pdf