• UVT-X3 Under-voltage Release
UVT-X3 Under-voltage Release

UVT-X3 Under-voltage Release

Product description:1. Major function To be assembled with the circuit breaker to achieve under-voltage protection 2. Parameters and performance Rated operation voltage Ue: AC240V Rated insulation voltage Ui: 500V Life: the operating life of the release is 400

1. Major function

To be assembled with the circuit breaker to achieve under-voltage protection
 

2. Parameters and performance

Rated operation voltage Ue: AC240V

Rated insulation voltage Ui: 500V

Life: the operating life of the release is ≥ 4000 cycles.

Action characteristics: when the applied voltage ≤35% Ue, the product should prevent circuit breaker from closing; when 35% Ue applied voltage 70% Ue, the product should operate and drive the circuit breaker open; when the applied voltage 85% Ue, the product should be able to close. The applied voltage should not exceed 110%Ue.